Conversion of ENV3 to Synchronous Condenser Unit
Modification of an existing 33 year old steam turbine driven 50 Hz, 850 MVA generator in order to allow it to be operated as a synchronous condenser at 150 kV level. The work involves design, manufacturing, erection and commissioning of the modification among others involving separation of steam turbine rotor and generator rotor, implementation of a thrust bearing, modification of generator radial bearing concept and implementation of a starting device (motor or static starting device) capable of running up the generator to the synchronous speed of 3000 rpm.